Complex Power
It is very conceptual and essential to understand. For establishing the expression of complex power, we have to first consider a single phase network that's voltage and current can be represented in complex form as V.ejα and I.ejβ. Where α and β are angles that voltage vector and current vector subtend with respect to some reference axis respectively. The active power and reactive power can be calculated by finding the product of voltage to conjugate of current. That means,
Therefore, the above equation cab be re-written as,
Where, P = VIcosφ and Q = VIsinφ.
This quantity S is called the complex power.
The magnitude of complex power i.e. |S| = (P2 + Q2)½ is known as the apparent power and its unit is volt-ampere. This quantity is a product of absolute value of voltage and current. Again absolute value of current is directly related to heating effect as per Joule's law of heating. Hence, rating of an electrical machine is normally determined by its apparent power carrying capability within allowable temperature limit.
It is noted that in the equation of complex power, the term Q [ = VIsinφ ] is positive when φ [= (α − β)] is positive that is, current lags the voltage which means the load is inductive in nature. Again Q is negative when φ is negative; that is current leads the voltage that means the load is capacitive.
Single Phase Power
A single phase electrical transmission system is practically not available, but still we should know the basic concept of single phase power first before going through modern three phase power system. Before going to details about single phase power, let's try to understand different parameters of electrical power system. Three basic parameters of electrical power system are electrical resistance, inductance and capacitance.Resistance
The resistance is an inherent property of any material, due to which it resists the flow of current by obstructing the movement of electrons through it due to collision with stationary atoms. The heat generated due to this process is dissipated and known as ohmic power loss. While current flows through a resistor ">resistor, there will not be any phase difference between the voltage and current, which means current and voltage are in same phase; the phase angle between them is zero. If I current flows through an electrical resistance R for t seconds, then total energy consumed by the resistor is I2.R.t. This energy is known as active energy and corresponding power is known as active power.Inductance
Inductance is the property by virtue of which an inductor stores energy in magnetic field during positive half cycle and gives away this energy during negative half cycle of single phase power supply. If a current 'I' flows through a coil of inductance L Henry, the energy stored in the coil in form of magnetic field is given byCapacitance
Capacitance is the property by virtue of which a capacitor stores energy in static electric field during positive half cycle and give away during negative half cycle of supply. The energy stored between two parallel metallic plates of electric potential difference V and capacitance across them C, is expressed asActive Power and Reactive Power
Let us consider a single phase power circuit in which current lags behind the voltage by an angle φ. Let the instantaneous electric potential difference v = Vm.sinωt Then the instantaneous current can be expressed as i = Im. sin(ωt - φ). Where, Vm and Im are the maximum values of sinusoidally varying electric potential difference and current respectively. The instantaneous power of the circuit is given byActive Power
Resistive Power
Let's take the condition first where the single phase power circuit is fully resistive in nature, that means the phase angle between voltage and current i.e. φ = 0 and hence,Reactive Power
Inductive Power
Now consider a situation when the single phase power circuit is fully inductive, that means the current lags behind the voltage by an angle φ = + 90°. Putting φ = + 90°
This can be concluded as if the circuit is purely inductive, energy will be stored as magnetic field energy during positive half cycle and give away during negative half cycle and rate at which this energy changes, expressed as reactive power of inductor or simply inductive power and this power will have equal positive and negative cycle and the net value will be zero.
Capacitive Power
Let us now consider the single phase power circuit is fully capacitive, that is the current leads the voltage by 90°, therefore φ = - 90°.Active Component and Reactive Component of Power
The power equation can be re-written asSingle Phase Power Equation for Purely Resistive Circuit
Let's examine single phase power calculation for purely resistive circuit. Circuit consisting of pure ohmic resistance is across a voltage source of voltage V, is shown below in the figure.
Substituting value of V(t) in above equation we get,
From equations (1.1) and (1.5) it is clear that V(t) and IR are in phase. Thus in case of pure ohmic resistance, there is no phase difference between voltages and current, i.e. they are in phase as shown in figure (b).
Instantaneous power,
From single phase power equation (1.8) it is clear that power consist of two terms, one constant part i.e.
and another a fluctuating part i.e.
That's value is zero for the full cycle. Thus power through pure ohmic resistor is given as and is shown in fig(c).
Single Phase Power Equation for Purely Inductive Circuit
Inductor is a passive component. Whenever AC passes through inductor, it opposes the flow of current through it by generating back emf. So, applied voltage rather than causing drop across it needs to balance the back emf produced. Circuit consisting of pure inductor across sinusoidal voltage source Vrms is shown in figure below.Single Phase Power Equation for Purely Capacitive Circuit
When AC passes through capacitor, it charges first to its maximum value and then it discharges. The voltage across capacitor is given as,Single Phase Power Equation for RL Circuit
A pure ohmic resistor and inductor are connected in series below as shown in fig (g) across a voltage source V. Then drop across R will be VR = IR and across L will be VL = IXL.Single Phase Power Equation for RC Circuit
We know that current in pure capacitance, leads voltage and in pure ohmic resistance it is in phase. Thus, net current leads voltage by angle of φ in RC circuit. If V = Vmsinωt and I will be Imsin(ωt + φ).Three Phase Power Definition
It is found that generation of three phase power is more economical than generation of single phase power. In three phase electric power system, the three voltage and current waveform are 120° offset in time in each cycle of power. That means; each voltage waveform has phase difference of 120° to other voltage waveform and each current waveform has phase difference of 120° to other current waveform. Three phase power definition states that in an electrical system, three individual single phase powers are carried out by three separate power circuits. The voltages of these three powers are ideally 120° apart from each other in time-phase. Similarly, the currents of these three powers are also ideally 120° apart from each other. Ideal three phase power system implies balanced system.
A three phase system is said to be unbalanced when either at least one of the three phase voltage is not equal to other or the phase angle between these phases is not exactly equal to 120°.
Advantages of Three Phase System
There are many reasons due to which this power is more preferable than single phase power.- The single phase power equation is
Which is time dependent function. Whereas three phase power equation is
Which is time independent constant function. Hence the single phase power is pulsating. This generally does not effect the low rating motor but in larger rated motor, it produces excessive vibration. So three phase power is more preferable for high tension power load.
- The rating of a three phase machine 1.5 times greater than that of same size single phase machine.
- Single phase induction motor has no starting torque, so we have to provide some auxiliary means of starting, but three phase induction motor is self starting-does not require any auxiliary means.
- Power factor and efficiency, both are greater in case of three phase system.
Three Phase Power Equation
For determination, the expression of three phase power equation i.e. for three phase power calculation we have to first consider an ideal situation where the three phase system is balanced. That means voltage and currents in each phase differ from their adjacent phase by 120° as well as the amplitude of each current wave is same and similarly amplitude of each voltage wave is same. Now, the angular difference between voltage and current in each phase of three phase power system is φ.
Then the voltage and current of red phase will be
VR = Vmsinωt and IR = Imsin(ωt − φ) respectively.
The voltage and current of yellow phase will be-
VY = Vmsin(ωt − 120°) and IY = Imsin(ωt − φ − 120°) respectively.
And the voltage and current of blue phase will be-
VB = Vmsin(ωt + 120°) and IB = Imsin(ωt − φ + 120°) respectively.
Therefore, the expression instantaneous power in red phase is -
Where, θ is the power angle which is kept very low due to stability reasons, Xl is the reactance of the transmission line, Vs is the sending end voltage and Vr is the receiving end voltage.
So, Qr becomes,
Now equation is formed as,
Solving we get,
Mathematically, the expression given for the reactive power
Note: We did not take negative sign as then Vr will become zero when Qr is zero which is not possible.
Let Q1 be the reactive power demanded by the load at the receiving end and Q2 be the reactive power supply from the generating or sending end. Then Qr is (Q1 - Q2).
Where, P is real power demand of the load (in watts).
In case the electrical power factor is to be decreased from cosθ2 to cosθ1, the reactive power which must be absorbed by the shunt reactor at the load end is given by,
The values of capacitance or inductor thus required can be calculated by using,

VR. IR = Vm. Imsinωt.sin(ωt − φ)
Similarly the expression instantaneous power in yellow phase is -
VY. IY = Vm.Imsin(ωt. − 120°)sin(ωt − φ − 120°)
Similarly the expression instantaneous power in blue phase is -
VB.IB = Vm.Imsin(ωt + 120°)sin(ωt − φ + 120°)
The total three phase power of the system is summation of the individual power in each phase-
P = VR.IR + VY. IY + VB. IB
= Vm.Imsinωt.sin(ωt − φ) + Vm.Imsin(ωt − 120°)sin(ωt − φ − 120°) + Vm.Imsin(ωt + 120°)sin(ωt − φ + 120°)
= Vm.Im[sinωt.sin(ωt − φ) + sin(ωt − °)sin(ωt − φ − 120°) + sin(ωt + 120°)sin(ωt − φ + 120°)]
= Vm.Im.(1/2)[2.sinωt.sin(ωt − φ) + 2.sin(ωt − 120°)sin(ωt − φ − 120°) + 2.sin(ωt + 120°)sin(ωt − φ + 120°)]
= Vm.Im.(1/2)[cos(ωt − ωt + φ) − cos(ωt + ωt − φ) + cos(ωt. − 120° − ωt. + 120° + φ) − cos(ωt − 120° + ωt − 120° − φ)
+ cos(ωt + 120° − ωt − 120°t + φ) − cos(ωt + 120° + ωt + 120° − φ)]
= Vm.Im.(1/2)[cosφ − cos(2.ωt − φ) + cosφ − cos(2.ωt − 240° − φ) + cosφ − cos(2.ωt + 240° − φ)]
= Vm.Im.(1/2)[3.cosφ − cos(2.ωt − φ) − cos(2.ωt − 240° − φ) − cos(2.ωt + 240° − φ)]
= Vm.Im.(1/2)[3.cosφ − cos(2.ωt − φ) − 2.cos(2.ωt − φ).cos(240°)]
= Vm.Im.(1/2)[3.cosφ − cos(2.ωt − φ) − 2.cos(2.ωt − φ).{−1/2}]
= Vm.Im.(1/2)[3.cosφ − cos(2.ωt − φ) + cos(2.ωt − φ)]
= 3.(Vm/√2).(Im/√2).cosφ
= 3VIcosφ This is three phase power equation
The above expression of power shows that the total instantaneous power is constant and equal to three times of the real power per phase. In case of single phase power expression we found that there are both reactive power and active power components, but in case of three phase power expression, the instantaneous power is constant. Actually in three phase system, the reactive power in each individual phase is not zero but sum of them at any instant is zero.
Reactive power is the form of magnetic energy, flowing per unit time in an electric circuit. Its unit is VAR (Volt Ampere Reactive). This power can never be used in an AC circuit. However, in an electrical DC circuit it can be converted into heat as when a charged capacitor or inductor is connected across a resistor, the energy stored in the element get converted to heat. Our power system operates on AC system and most of the loads used in our daily life, are inductive or capacitive, therefore reactive power is a very important concept from electrical perspective.
The electrical power factor of any equipment determines the amount of reactive power it requires. It is the ratio of real or true power to the total apparent power required by an electrical appliance. These powers can be defined as,
Apparent Power(P) = V(Voltage) × I(Current)
Real Power (P) = V(Voltage) × I(Current) × cosθ
Real Power (P) = V(Voltage) × I(Current) × cosθ
Where, θ is the phase difference between voltage and current and cosθ is electrical power factor of the load.
Reactive Power (Q) = V(Voltage) × I(Current) × sinθ
Reactive power is always present in a circuit where there is a phase difference between voltage and current in that circuit, such as all our domestic loads are inductive. So, there is a phase difference between voltage and current, and the current lags behind the voltage by certain angle in time domain. An inductive component takes the lagging reactive power and a capacitive component absorbs the leading reactive power, here lagging reactive power refers to magnetic energy and leading reactive power refers to electrostatic energy.
In a typical AC circuit, such as RL circuit (Resistive + Inductive) or RC circuit (Resistive + Capacitive), the reactive power is taken from the supply for a half cycle and returned to the supply for next half cycle. For example power consumed for an RL load is derived as:
V = Vmsinωt , I = Imsin(ωt − θ)
Here, Q1sin2ωt is reactive power that's average value is zero, this shows that reactive power is never utilized.